A Static Var Generator (SVG) is a new-generation reactive power compensation and power quality management device based on modern power electronics technology (IGBT) and digital signal processing technology. It can replace traditional capacitor banks, reactors, and SVCs (Static Var Compensators), real-time detecting and dynamically compensating for reactive power, harmonic currents, and three-phase unbalance in the power grid—thereby stabilizing system voltage, improving power factor, and reducing line losses. It achieves millisecond-level ultra-fast response and continuous stepless adjustment, providing an efficient and reliable solution for grid upgrades, harmonic mitigation, and refined energy management.
Power Quality
BRN-SVG
BRN-SVG supports full-range reactive power compensation, harmonic mitigation, and three-phase unbalance governance. Adopting a three-level topology and intelligent air cooling design, it is highly suitable for efficient power quality optimization in medium and low voltage distribution networks, industrial automation, smart buildings, and data centers.
Shanghai Brilliant Automation's BRN-SVG series is a high-performance Static Var Generator, available in a modular rack-mounted design. This series covers voltage levels of 200V/400V/480V/690V, with single-module capacity ranging from 35kVar to 150kVar (120kVar for 690V). Adopting a three-level topology and 20kHz switching frequency, it delivers an extremely fast response time of ≤10ms and supports continuously adjustable capacitive and inductive reactive power. The device supports open-loop/closed-loop CT installation, can be wired in three-phase three-wire/three-phase four-wire configurations, and features comprehensive overload capability (110% rated current for continuous operation, 120% rated current for 1 minute). It supports multi-module parallel connection (up to 8 units under HMI control, up to 20 modules in parallel), with redundancy design and unbalance governance capability. It is highly suitable for substations, industrial automation, smart buildings, and data centers, and is designed to support grid upgrades, harmonic mitigation, and refined energy management.
- Electrical Parameters: Rated voltage 200V/400V/480V/690V; Single module capacity 35kVar~150kVar (120kVar for 690V); Frequency 50/60Hz; Supports three-phase three-wire/three-phase four-wire wiring.
- Compensation Performance: Continuously adjustable capacitive and inductive reactive power; Response time ≤10ms; Capable of three-phase unbalance governance; Supports open-loop or closed-loop CT installation (closed-loop recommended for parallel operation).
- Core Functions: Adopts three-level topology, 20kHz switching frequency; Supports multi-module parallel connection (up to 8 units under HMI control, up to 20 modules in parallel); Features redundancy design and SVC function expansion.
- Display & Communication: Optional 4.3-inch/7-inch screen or HMI control; Communication interfaces include RS485, CAN protocol, and RJ45 port, supporting remote monitoring and multi-protocol communication.
Overview
BRN-SVG adopts an advanced three-level topology and intelligent air cooling design. The three-level topology effectively reduces switching losses and output harmonics, improving overall efficiency and reliability. The intelligent air cooling automatically adjusts fan speed based on the internal temperature of the module, reducing noise and energy consumption while ensuring heat dissipation. This design enables BRN-SVG to adapt to harsh industrial environments, ensuring stable operation within a wide temperature range of -45°C to 55°C.
IEC 61000-6-4 is an international standard developed by the IEC, aimed at specifying electromagnetic compatibility (EMC) emission limit requirements for electrical and electronic equipment in industrial environments.
Diagram
Reference wiring and deployment views for installation planning and system integration.
Product Map
Hardware layout reference for interface identification and installation planning.
Key Specs
Core performance highlights for specification review and project planning.
Measurement Accuracy
Adopts a three-level topology and 20kHz switching frequency, providing a fast response time of ≤10ms, achieving continuously adjustable compensation for both capacitive and inductive reactive power, and ensuring high-precision power quality monitoring and management.
Harmonic Analysis
Features powerful harmonic management capabilities, supports three-phase three-wire/four-wire systems, effectively identifies and compensates for system reactive power, and improves system reliability (Note: Please refer to the actual selected configuration for specific harmonic orders).
Waveform & Event Recording
Built-in intelligent control unit, supports overload protection (110% rated current for continuous operation, 120% rated current for 1 minute), and is equipped with an RS485 communication interface to capture operating data for faster diagnosis and troubleshooting.
System Integration
Supports modular parallel connection (≤20 modules in parallel), integrates with SCADA, BMS, and EMS platforms via standard Modbus communication protocol, and offers optional 4.3-inch or 7-inch HMI touch screens for local monitoring.
Accessories
Operation Panel
The BRN-SVG and BRN-APF series from BRN are equipped with a high-performance industrial HMI touch panel as standard. It integrates real-time data display, parameter configuration, fault recording, and status monitoring. With an intuitive interface, easy operation, multi-language support, and excellent EMC performance, it ensures stable operation in complex power distribution environments and delivers an efficient, intelligent HMI experience.
USB-to-RS485 Converter
This plug-and-play USB to Serial RS485 Converter is designed to provide a convenient and reliable connection from Brilliant meters or motor controllers to other devices with a USB port.
UL 508A Panel Shop
Pre-configured, pre-wired panel solution is ideal for on-site installations need to meet regional regulatory safety and environmental compliance. All panels are quality tested to be reliable and fault-free.
AC Current Transformers
An AC current transformer (CT) is a crucial measuring device in power systems. Operating on the principle of electromagnetic induction, it proportionally converts high primary currents into standardized low secondary currents (typically 5A or 1A) for use by meters and protective relays. Its primary functions are to provide electrical isolation from high-voltage circuits, ensuring safety, and to extend the range of measuring instruments. It is an essential component for power monitoring and revenue metering.
Inline Fuse
In-line fuse holders are used in places with spatial constraints to provide circuit protection in the event of a fault. It is designed to be safe to the touch and flexible for use in different types of applications.
Test Lead & Voltage Clip
A 4-color (yellow, green, red, black) test lead set featuring standard banana plugs for secure connections and durable flexible insulation. Specially designed for voltage measurement, circuit testing, and multi-channel wiring. The bright color-coding ensures quick identification, making it an essential diagnostic tool for engineers and electronics enthusiasts.
Frequently Asked Questions
Common questions on wiring, setup, and commissioning.
The BRN-SVG is a Static Var Generator used in power systems. It dynamically compensates for reactive power in the grid by continuously adjusting capacitive and inductive reactive power to stabilize voltage, improve power factor, and enhance power quality.
It is widely used in industrial power distribution, commercial buildings, and power systems. It is particularly suitable for scenarios with fast-changing loads that require dynamic reactive power compensation, such as power grids with impact loads like welding equipment, rolling mills, and hoists.
According to the technical parameters, the response time of the BRN-SVG is less than or equal to 10 milliseconds (≤10ms), allowing it to track load changes and compensate extremely quickly.
It supports three-phase three-wire and three-phase four-wire systems, adapting to different grid configuration requirements.
The BRN-SVG adopts intelligent air cooling. During installation, sufficient air circulation must be ensured, adequate air inlet area and front/rear door panel opening dimensions must be reserved (refer to the heat dissipation requirements table in the manual), and the ambient temperature must be within the specified range.
The equipment must be installed in an electrical control room or a well-ventilated indoor environment. The floor must be flat and dry, and water accumulation is strictly prohibited. It should be kept away from flammable and explosive materials and corrosive gases. If there is severe dust or conductive dust in the environment, special protective treatment is recommended.
It is recommended to select a CT with an accuracy of Class 0.5 or above and a secondary power greater than 1VA. The CT ratio range is typically 50/5 to 20000/5. The specific ratio is recommended to be selected based on 1.2 to 1.5 times the system current. For example, if the transformer capacity is 2000kVA, a 3000/5 CT is recommended.
It is recommended to install the external CT on the load side. This allows for more accurate detection of the load's reactive power demand and compensation. It can also be used if installed on the power supply side, but ensure the wiring direction is correct.
The CT wiring direction determines whether the equipment can correctly determine the current phase. If the direction is reversed, it may result in poor compensation effects or equipment failure. The manual notes that if the transformer orientation is opposite to the default setting, the "CT direction" setting needs to be changed via the HMI screen.
Operating the equipment when the CT circuit is open is strictly prohibited. An open secondary side of the CT will generate high voltage, which is extremely dangerous and may cause equipment damage or personal injury. Before maintenance, always short-circuit the CT secondary side first.
Yes. Multiple modules can be connected in parallel. The number of parallel modules can reach up to 20, and no more than 8 modules can be combined under HMI control. When connecting in parallel, the principle of "top to top, bottom to bottom" must be followed.
The large screen is connected to the RS485 upper port of Module 1 via a customized DB9 cable. The RS485 connections between subsequent modules follow the cascading principle of "top to bottom, bottom to top." The large screen power can be external or drawn from the module's DC24V terminal.
Before maintenance, the main power supply must be disconnected, and wait at least 15 minutes to ensure the internal capacitors are fully discharged to 0V. Maintenance personnel must wear insulating protective equipment, and only personnel with electrical qualifications are allowed to operate.
Common faults include: IGBT hardware overcurrent, bus overvoltage/undervoltage, module overheating, CT wiring errors, or fan failures. Most faults can be resolved by resetting or restarting. If they cannot be resolved, contact the manufacturer's technical support.
According to the technical parameters, the protection level of the BRN-SVG module is IP20, making it suitable for installation in standard electrical cabinets or control rooms.
Daily checks include whether the input/output voltage and current are normal, listening for abnormal sounds, and checking if terminal blocks are loose or aged. It is recommended to check cables and terminals quarterly, and inspect the appearance and internal temperature semi-annually.